The OEM Motoric Valve Drive 6: 24 V Proportional Failsafe can be delivered with a custom setting. The properties can be changed subsequently via app. (→ Chapter App functions)
Function | Default | Optional |
Force Actuation force | 125 N | 100 N 125 N 150 N 200 N |
Runtime Running time | 15 s/mm | 15 s/mm 30 s/mm |
Valve stroke recognition Valve path recognition | ON | ON OFF (OFF= MPRF mode) |
Display illumination Display lighting | ON | ON OFF |
Drive path Stroke | 8.5 mm | 2 mm … 8.5 mm (steps of 0.1 mm) |
Valve position Valve path display | % | % mm |
Failsafe position only for Failsafe variants | 0 % | 0 % … 100 % |
Valve Curve Valve curve | Linear | Linear EQP |
Bypass Minimum valve position | 0 % | 0 % … 50 % (steps of 1 %) |
FB Range (stem dn – stem up) Feedback | 1 – 9 V | 1 – 9 V 1 – 5 V 0 – 10 V |
Control voltage – start Control voltage – start | 0.5 V | 0 V … 10 V (steps of 0.1 V) |
Control voltage – end Control voltage – end | 10 V | 0 V … 10 V (steps of 0.1 V) |
Actuator Mode | MPx | MPx | M3x |
Control voltage – start: 10
Control voltage – end: 0 negates the path