The OEM Motoric Valve Drive 6: 24 V Proportional can be delivered with a custom setting. The properties can be changed subsequently via app. (→ Chapter App functions)
| Function | Default | Optional |
| Force Actuation force | 125 N | 100 N 125 N 150 N 200 N |
| Runtime Running time | 15 s/mm | 15 s/mm 30 s/mm |
| Valve stroke recognition Valve path recognition | ON | ON OFF (OFF= MPR mode) |
| Display illumination Display lighting | ON | ON OFF |
| Drive path Stroke | 8.5 mm | 2 mm … 8.5 mm (steps of 0.1 mm) |
| Valve position Valve path display | % | % mm |
| Valve curve Valve curve | Linear | Linear EQP |
| Bypass Minimum valve position | 0 % | 0 % … 50 % (steps of 1 %) |
| FB range (stem dn – stem up) Feedback | 1 – 9 V | 1 – 9 V 1 – 5 V 0 – 10 V |
| Control Voltage (stem down) Control voltage – start | 0.5 V | 0 V … 10 V (steps of 0.1 V) |
| Control Voltage (stem up) Control voltage – end | 10 V | 0 V … 10 V (steps of 0.1 V) |
| Actuator Mode | MPx | MPx / M3x |
Control voltage – start: 10
Control voltage – end: 0 negates the path
| Function | Default | Optional |
| Force Actuation force | 125 N | 100 N 125 N 150 N 200 N |
| Runtime Running time | 15 s/mm | 15 s/mm 30 s/mm |
| Valve stroke recognition Valve path recognition | OFF (M3P) / ON (M3V) | OFF / ON |
| Display illumination Display lighting | ON | OFF ON |
| Actuator Mode | M3x | M3x MPx |