Connections and indications #
1 – Boiler connection
2 – Pump connection
3 – Protective earth connection (230 V only)
4 – Voltage supply
5 – Fuse
6 – Temperature limiter or dew point monitor
7 – Changeover heating/cooling
8 – Setback temperature channel external timer
9 – Thermostat connection
10 – LED
11 – NFC antenna
12 – Connection of valve drives
13 – Strain relief
Technical data #
Operating voltage | 24 V ±20 %, 50 Hz, 230 V ±10 %, 50 Hz |
Power consumption | max. 50 VA |
Power consumption (idle) | <1 W |
Fuse | 24 V: T2A 230 V: T4AH |
Connectable room controllers | max. 8 |
Connectable room controllers | A 20×05, AST 20×05, A 40×05, AST 40×05 |
Connectable valve drives | max. 12 actuators |
Inrush current per valve drive | 230 V: max. 500 mA |
max. permissible nominal load of the connectable valve drives | 24 V: max. 24 W |
Pump connection Switching capacity | 2 A, 200 VA induktiv |
– Turn-on delay | parametrisable (default: 2 minutes) |
– Follow-up time | parametrisable (default: 2 minutes) |
Boiler connection Switching capacity | 2 A, 200 VA induktiv |
– Turn-on delay | parametrisable (default: 0 parametrisable ) |
– Follow-up time | parametrisable (default: 0 parametrisable ) |
Pump protection | parametrisable (default: 3 days / 5 min.) |
Valve protection | parametrisable (default: 3 days / 5 min.) |
Valve drive operating principle | NC |
Ambient temperature | 0 … 50 °C |
Storage temperature / transport temperature | -20 … +70 °C |
Ambient humidity | 5-80 %, non-condensing |
ERP class according to EU 811/2013 | 1=1 % |
Contamination degree | 2 |
Rated impulse voltage | 1500 V |
Protection class | 24 V: III 230V: II |
Protection type: | IP20 |
Function | Type 1 / type 1.C |
Dimensions (H x W x D) | 90 x 326,5 x 52 mm |
Display #
LED heating zones | green (one LED per HZ) |
LED fuse | red |
LED power | green / red (two-coloured) |
LED pump | green |
LED boiler | green |
LED heating / cooling | green |
LED Modbus | Flashing orange for Modbus activity |