The feedback signal of the OEM Motoric Valve Drive 6: 24 V Proportional Failsafe enables direct feedback of the current operating status to the DDC system via a 0 to 10 V signal. Voltages from 1 to 9 V provide information about the actuator position: Voltages 9.5 V indicate errors that have occurred. The connection of the feedback signal is voltage resistant up to 24 V.
MPxF
Mode 1 – 9 | Mode 0 – 10 | Mode 1 – 5 | Description |
< 0.5 V | | < 0.5 V | No contact |
1 – 9 V | 0 – 10 V | 1 – 5 V | Proportional to stroke |
> 9.5 V | | > 9.5 V | Internal error |
5 V | 15 V | 5 V | During initialisation |
.NOTE.
The bandwidth of the output voltage can be changed to 0 – 10 V in the settings. This eliminates the need for error evaluation.