The OEM Motoric Valve Drive: 24 V Modbus RTU can be delivered with a custom setting. The properties can be changed subsequently via app. (→ Chapter App functions)
Function | Default | Optional |
Mode | MPM | |
Force Actuation force | 125 N | 100 N 125 N 150 N 200 N |
Runtime Running time | 15 s/mm | 15 s/mm 30 s/mm |
Valve stroke recognition Valve path recognition | ON | ON OFF |
Display illumination Display lighting | ON | ON OFF |
Drive path Stroke | 8.5 mm | 2 mm … 8.5 mm (in steps of 0.1 mm) |
Valve position Valve path display | % | % mm |
Baud rate | 19.200 | 4.800 9.600 19.200 |
Parity | Even | None Even Odd |
Address Modbus address | 1 | 1 – 247 |