Alpha direct Balance base station

  • Device overview
  • Intended use
  • Electric connection
  • Automatic hydraulic balancing
  • Commissioning mode
  • Montage
  • Maintenance
  • Dismantling

Alpha direct Balance Switch NFC base station

  • Register description
  • Automatic hydraulic balancing
  • Electric connection
  • Maintenance
  • Dismantling
  • LED signaling

Alpha direct Balance Downloads

  • Alpha direct Balance Downloads
  • Alpha direct Balance Downloads
  • Alpha direct Balance Switch Downloads
  • Certificates
  • Data sheets

Alpha direct Balance FAQs

  • Is the OEM Alpha direct Balance System compatible with other thermostat components with their own controls?
  • Can any thermostats be used with the base station?
  • Does the OEM Alpha direct base station need to be calibrated?
  • Is the base station capable of cooling?
  • Do circuit control valves or other balancing devices need to be fitted to the distribution network?
  • Can a boiler be controlled?
  • Can the OEM Alpha direct Balance open the thermostat valve periodically during the summer to stop it from getting stuck?
  • Are flow indicators still required for the OEM Alpha direct Balance System?
View Categories
  • Systamauswahl
  • Systemauswahl
  • Alpha direct Balance Switch
  • Alpha direct Balance base station
  • Device overview

Device overview

Connections and displays 230 V #

1 – Boiler connection
2 – Pump connection
3 – Protective conductor connection (only for 230 V)
4 – Voltage supply
5 – Fuse
6 – Temperature limiter or dew point sensor
7 – Heating/cooling change-over
8 – Reduction channel, external timer
9 – Thermostat connection
10 – LED
11 – DIP switch “disable cooling”
12 – Connection of actuators
13 – Strain relief

Technical data #

Operating voltage:24 V ±20 %, 50 Hz,
230 V ±10 %, 50 Hz
Power consumption:max. 50 VA
Power consumption (idle):<1 W
Fuse:24 V: T2A / 230 V: T4AH
Connectable room thermostats:max. 8
Connectable actuators, type:A 20×05, AST 20×05, A 40×05, AST 40×05
Connectable actuators:max. 17 actuators
The following applies to other actuators than those mentioned above
Inrush current per actuator:230 V: max. 500 mA
max. permitted nominal load
of the connectable actuators:
24 V: max. 24 W
Pump control switching power:2 A, 200 VA induktiv
Switch-on delay:2 minutes
Follow-up time:2 minutes
Boiler control switching power:2 A, 200 VA induktiv
Switch-on delay:2 minutes
Follow-up time:2 minutes
Pump protection function:3 days / 5 min.
Valve protection function:16 days / 5 min.
Control direction of actuators:NC
Ambient temperature:0 to 50 °C
Storage temperature:-20 to 70 °C
Ambient humidity:80 %, non-condensing
ERP class acc. to EU 811/2013:1=1 %
Contamination degree:2
Rated surge voltage:1500 V
Protection class:24 V: III / 230V: II
Protection type:IP 20
Function:Type 1 / type 1.C
Dimensions (H x L x D):90 x 326,5 x 52 mm
Updated on September 17, 2024