Skip to content
Logo
  • English
    • German

Alpha direct Balance base station

  • Device overview
  • Intended use
  • Electric connection
  • Automatic hydraulic balancing
  • Commissioning mode
  • Montage
  • Maintenance
  • Dismantling

Alpha direct Balance Switch NFC base station

  • Register description
  • Automatic hydraulic balancing
  • Electric connection
  • Maintenance
  • Dismantling
  • LED signaling

Alpha direct Balance Downloads

  • Alpha direct Balance Downloads
  • Alpha direct Balance Downloads
  • Alpha direct Balance Switch Downloads
  • Certificates
  • Data sheets

Alpha direct Balance FAQs

  • Is the OEM Alpha direct Balance System compatible with other thermostat components with their own controls?
  • Can any thermostats be used with the base station?
  • Does the OEM Alpha direct base station need to be calibrated?
  • Is the base station capable of cooling?
  • Do circuit control valves or other balancing devices need to be fitted to the distribution network?
  • Can a boiler be controlled?
  • Can the OEM Alpha direct Balance open the thermostat valve periodically during the summer to stop it from getting stuck?
  • Are flow indicators still required for the OEM Alpha direct Balance System?
View Categories
  • Systamauswahl
  • Systemauswahl
  • Alpha direct Balance Switch
  • Alpha direct Balance base station
  • Electric connection

Electric connection


Warning! Electrical voltage! Danger to life!
Always disconnect the base from the mains network and secure against unintended activation before opening.
Disconnect external voltages and secure against unintended activation.

Regulators with TRIAC switching element that generate a leakage current at the output,
are not compatible with this system.


For the connection of the power supply, the cable cross-sections must be 0.75 mm² – 1.5 mm² for 24 V or 1.5 mm² for 230 V. Depending on the voltage version of the base, it is possible to take L1 and L2, or L and N, as well as the protective conductor, from the base. A temperature limiter/dew point sensor can be connected to the TB/%H contact. If this contact is not used, it must be bridged (provided for at the factory). The bridge must be removed when a connection is established at contact is TB/%H. The temperature limiter/dew point sensor must be designed as a normally closed contact. DIP switches 1-8 “Disable cooling” are set to “Off” ex works. On” can be used for
every HZ cooling can be blocked.

For systems that are operated in cooling mode, the “Block cooling” function must be set to ON on all unoccupied heating zones using the DIP switch. If the DIP switch is set to OFF, the corresponding output is not switched off and the pump and boiler contacts remain activated. The external system clock transmits the input signal to the connected thermostats.


The 24 V version of the base must be supplied via a safety transformer in accordance with EN 61558-2-6 or a Class II transformer in accordance with UL for North America.