  • Is the OEM Alpha direct Balance System compatible with other thermostat components with their own controls?
  • Can any thermostats be used with the base station?
  • Does the OEM Alpha direct base station need to be calibrated?
  • Is the base station capable of cooling?
  • Do circuit control valves or other balancing devices need to be fitted to the distribution network?
  • Can a boiler be controlled?
  • Can the OEM Alpha direct Balance open the thermostat valve periodically during the summer to stop it from getting stuck?
  • Are flow indicators still required for the OEM Alpha direct Balance System?
View Categories
  • Systamauswahl
  • Systemauswahl
  • Alpha direct Balance Switch
  • Alpha direct Balance Switch NFC base station
  • Electric connection

Electric connection


Warning! Electrical voltage! Danger to life!
Always disconnect the base from the mains network and secure against unintended activation before opening.
Disconnect external voltages and secure against unintended activation.

For the connection of the power supply, the cable cross-sections must be 0.75 mm² – 1.5 mm² for 24 V or 1.5 mm² for 230 V. Depending on the voltage version of the base, it is possible to take L1 and L2, or L and N, as well as the protective conductor, from the base. A temperature limiter/dew point sensor can be connected to the TB/%H contact. If this contact is not used, it must be bridged (provided for at the factory). The bridge must be removed when a connection is established at contact is TB/%H. The temperature limiter/dew point sensor must be designed as a normally closed contact.
The activation of the special functions as well as the setting of “Disable cooling” and the assignment of the inputs to the outputs can only be set via the app. The external system clock transmits the input signal to the connected thermostats.


The power supply for the 24 V version of the base must be provided by a safety transformer.
according to EN 61558-2-6 or a Class II transformer according to UL for North America.


The following parameters can be set via the app:

Switch-on delay of the pumpdefault: 2 minutes
Pump follow-up timedefault: 2 minutes
Switch-on delay of the boilerdefault: 0 minutes
Nachlaufzeit Boilerdefault: 0 minutes
Maximum inactive time of the pump before the pump protection function starts default: 3 days
Activation time of the pump (pump protection function) default: 5 minutes
Maximum inactive time of the valve before the valve protection function starts default: 16 days
Valve actuation time (valve protection function)default: 5 minutes

If the base station is configured in a de-energized state, these changes are not applied until the next time power is applied.

A room controller can be assigned to each actuator. Options in the app:

  • Adjustment of the listed factory settings
  • Assignment of names for the corresponding rooms
ActuatorsRoom thermostat
1 + 21
3 + 42
5 + 63
7 + 84
95
106
117
128
Updated on April 17, 2024