title: App functions
description: "| **FUNCTION** | **DESCRIPTION** | **DISPLAY** | | --- | --- | --- | | DEVICE OPERATIONS | | | | **Read** | | | | Read from device | Reading out the settings of the OEM Motoric Valve Drive…"
url: "https://faqdoc.info/en/systemauswahl/motoric-valve-drive-6/motoric-valve-drive-24-v-am3-en/app-functions-2/"
updated: "2024-05-13"
category: Motoric Valve Drive 24 V (AM3)
---

# App functions

| **FUNCTION** | **DESCRIPTION** | **DISPLAY** |
| --- | --- | --- |
| DEVICE OPERATIONS |  |  |
| **Read** |  |  |
| Read from device | Reading out the settings of the OEM Motoric Valve Drive 6: 24 V Proportional | – Ready to scan: **Hold your smartphone near to NFC tag** – Display: **Data was read successfully** or **Error message** → Repeat the process: The mobile device was moved too early or should be aligned more precisely. |
| Read from file | **Prerequisite for use:** File stored on the mobile device. – Reading the settings from a file stored on the mobile device Ways to store a file on the mobile device: – Sending files as attachments by message or e-mail – Storage of file by **Write to file** command | Display of the file management of the mobile device |
| **Write** |  |  |
| Write to device | Settings are written to the OEM Motoric Valve Drive 6: 24 V Proportional | – Ready to scan: **Hold your smartphone near to NFC tag** – Display: **Data was read successfully** or **Error message** → Repeat the process: The mobile device was moved too early or should be aligned more precisely. |
| Write to file | Scanned settings are stored as a file in the memory of the mobile device. The file can be used for – the dispatch by message or mail - the setup of further OEM Motoric Valve Drive 6: 24 V Proportional devices | Display of the file management of the mobile device |
| **Verify** |  |  |
| Verify device | Comparison of the settings displayed in the **Settings**menu and the settings in the OEM Motoric Valve Drive 6: 24 V Proportional | – Ready to scan: **Hold your smartphone near to NFC tag** – Display: **Data was read successfully** or **Error message** → Repeat the process: The mobile device was moved too early or should be aligned more precisely. Result: **Validation successful**: identical settings or **Verification failed**: different settings |
| **Active operations** |  |  |
| Start initialization | Initialization of the OEM Motoric Valve Drive 6: 24 V Proportional The actuator travels along the actuator path and valve path. The opening and closing points of the valve are stored. | **Your device will now begin with the initialization process.** |
| Go to position | Setting the actuator position | Sequence: 1. **Go to position** 2. **Confirm** 3. Ready to scan: **Hold your smartphone near to the NFC tag.** 4. **your device will now go to the specified position** or **Error message** → Repeat the process: The mobile device was moved too early or should be aligned more precisely. |
| Factory reset | Adjusts the parameters of the OEM Motor-ic Valve Drive 6: 24 V Proportional to the delivery state. | Sequence: 1. Warning message 2. Scan process |
| **Settings** |  |  |
| Force | Setting the force in the levels: 100 N, 125 N, 150 N, 200 N |  |
| Runtime | 15 s/mm, 30 s/mm |  |
| Valve path recognition (VPR) | ON \| OFF |  |
| Display illumination | ON \| OFF | Turns the LCD backlight on or off. |
| Drive path | 2 – 8.5 mm | Limitation of the actuator path when the VPR is switched off. Use as a "limiter". |
| Bypass | 0 ... 50 % | Limitation of the actuator travel in the other direction. **Application:** Ensure minimum flow to protect against frost. **Note:** Both the rubber diaphragm in the valve and the backlash in the adapter and the gear unit can influence the position. Please check the position! |
| Valve position | mm \| % | Sets the preferred display on the LC display. |
| Failsafe position | 0 % | 0 ... 100 %, steps of 10 % (only for MPxF) |
| Valve Curve Valve curve | Linear | Linear \| EQP |
| Feedback range Functionality | 1 – 9 V | 1 - 9 V \| 1 - 5 V \| 0 - 10 V |
| Control voltage – start Control voltage – start | 0.5 V | 0 V ... 10 V (steps of 0.1 V) |
| Control voltage end Control voltage – end | 10 V | 0 V ... 10 V (steps of 0.1 V) |
| **Device Operations** |  |  |
| Mode | **MPx** | MPx \| M3x |

**.NOTE.**
All modifications must only be carried out with the appropriate expertise. Incorrect settings can lead to malfunctions of the drive, a malfunction of the control system and consequential costs. The manufacturer does not accept any responsibility for incorrect settings and their consequences.
**Changes are accepted after the actuator is switched on again.**

---

**Adjustable modes**

|  | **Function** | **Valve path** | **Description** |
| --- | --- | --- | --- |
| **MPR** | Proportional | preset, fixed | - Valve path recognition switched off, path fixed |
| **MPV** | Proportional | Valve path recognition | - 3-pole connection cable without feedback - The feedback signal can be tapped in all proportional modes with 4-wire connection cable |
| **M3P** | 2- and 3-point operation | Valve path recognition **deactivated** | The motor switches off when the valve pressure plate has reached the inner, mechanical stop |
| **M3V** | 2- and 3-point operation | Valve path recognition **activated** | The motor shuts down when the valve pressure plate lifts off the plunger **Caution**: Without back pressure from the valve, the valve pressure plate only extends! |

By changing the mode, the OEM Motoric Valve Drive 6: 24 V Proportional can also behave like a 2-/3-point actuator: