title: Error codes
description: "Errors are indicated by an error code. The subsequent table explains the different error codes and error corrections. | **Error code** | **Meaning** | **Description** | **Error correction** | | --- | --- | --- | --- | | 0…"
url: "https://faqdoc.info/en/systemauswahl/motoric-valve-drive-6/motoric-valve-drive-6-24-v-modbus-en/error-codes-2/"
updated: "2024-06-04"
category: "Motoric Valve Drive 6: 24 V modbus"
---

# Error codes

Errors are indicated by an error code. The subsequent table explains the different error codes and error corrections.

| **Error code** | **Meaning** | **Description** | **Error correction** |
| --- | --- | --- | --- |
| 0 | No error | This is no error |  |
| 7 | Stall | Blockage during initialization run at non-permitted position | 1. Disconnect actuator from voltage supply 2. Move the actuator shaft with the manual adjuster out of the end position 3. Re-initialization after switching on the voltage supply again In case of repeated occurrence of the fault, the customer service must be consulted. |
| 8 | Low motor current | Motor current too low | 1. Re-initialization by switching the actuator off and on again If the fault cannot be rectified automatically after a maximum of three attempts, contact the customer service. |
| 9 | Max move Reached | Driving too long in one direction | 1. Re-initialization by switching the actuator off and on again If the fault cannot be rectified automatically after a maximum of three attempts, contact the customer service. |