title: App functions
description: "| **FUNCTION** | **DESCRIPTION** | **DISPLAY** | | --- | --- | --- | | DEVICE OPERATIONS | | | | **Read** | | | | Read from device | Reading out the settings of the OEM Motoric Valve Drive…"
url: "https://faqdoc.info/en/systemauswahl/motoric-valve-drive-6/motoric-valve-drive-6-24-v-proportional-failsafe-en/app-functions/"
updated: "2024-04-15"
category: "Motoric Valve Drive 6: 24 V proportional failsafe"
---

# App functions

| **FUNCTION** | **DESCRIPTION** | **DISPLAY** |
| --- | --- | --- |
| DEVICE OPERATIONS |  |  |
| **Read** |  |  |
| Read from device | Reading out the settings of the OEM Motoric Valve Drive 6: 24 V Proportional Failsafe | - Ready to scan: **Hold your smartphone near to the NFC tag** - Display: **Data was read successfully** or **Error message** → Repeat the process: The mobile device has been moved too early or must be aligned more precisely. |
| Read from file | **Prerequisite for use:** File stored on the mobile device. - Reading the settings from a file stored on the mobile device Ways to store a file on the mobile device: - Sending files as attachments by message or mail - Storage of file by **Write to file** command | Display of the file management of the mobile device |
| **Write** |  |  |
| Write to device | Settings are written to the OEM Motoric Valve Drive 6: 24 V Proportional Failsafe | - Ready to scan: **Hold your smartphone near to NFC tag** - Display: **Data was read successfully** or **Error message** → Repeat the process: The mobile device has been moved too early or must be aligned more precisely. |
| Write to file | Scanned settings are stored as a file in the memory of the mobile device. The file can be used for - the dispatch by message or mail - the setup of further OEM Motoric Valve Drive 6: 24 V Proportional Failsafe de-vices | Display of the file management of the mobile device |
| **Verify** |  |  |
| Verify device | Comparison of the settings displayed in the Settings menu and the settings in the OEM Motoric Valve Drive 6: 24 V Proportional Failsafe | - Ready to scan: **Hold your smartphone near to the NFC tag** - Display: **Data was read successfully** or **Error message** → Repeat the process: The mobile device was moved too early or must be aligned more precisely. The result: **Validation successful**: identical settings or **Verification failed**: different settings |
| **Active operations** |  |  |
| Start initialization | Initialization of the OEM Motoric Valve Drive 6: 24 V Proportional Failsafe The actuator travels along the actuator path and the valve path. The opening and closing points of the valve are stored. | **Your device will now begin with the initialization process.** |
| Go to position | Setting the actuator position | Sequence: 1. **Go to position** 2. **Confirm** 3. Ready to scan: **Hold your smartphone near to the NFC tag.** 4. **Your Device will now go to the specified position**. or **Error message** → Repeat the process: The mobile device has been moved too early or must be aligned more precisely. |
| Factory reset | Adjusts the parameters of the OEM Motoric Valve Drive 6: 24 V Proportional Failsafe to the delivery state. | Sequence: 1. Warning message Scan process |
| **Settings** |  |  |
| Force | Setting the force in the levels: 100 N, 125 N, 150 N, 200 N |  |
| Runtime | 15 s/mm, 30 s/mm |  |
| Valve stroke recognition (VSR) | ON \| OFF |  |
| Display illumination | ON \| OFF | Turns the LCD backlight on or off. |
| Drive path | 2 – 8.5 mm | Limitation of the actuator path when the VPR is switched off. Use as a "limiter". |
| Bypass | 0 … 50 % | Limitation of the actuator travel in the other direction. **Application:** Ensure minimum flow to protect against frost. **Note:**Both the rubber diaphragm in the valve and the backlash in the adapter and the gear unit can influence the posi-tion. Please check the position! |
| Display Valve path Valve path display | % | % \| mm |
| Failsafe position | 0 % | 0 … 100 % (steps of 10 %) |
| Valve curve Valve curve | Linear | Linear \| EQP |
| Feedback range Functionality | 1 – 9 V | 1 – 9 V \| 1 – 5 V \| 0 – 10 V |
| Control voltage – start Control voltage – Start | 0.5 V | 0 V … 10 V (steps of 0.1 V) |
| Control voltage – end Control voltage – end | 10 V | 0 V … 10 V (steps of 0.1 V) |