The feedback signal of the OEM Motoric Valve Drive 6: 24 V Proportional Failsafe enables direct feedback of the current operating status to the DDC system via a 0 to 10 V signal. Voltages from 1 to 9 V provide information about the actuator position: Voltages 9.5 V indicate errors that have occurred. The connection of the feedback signal is voltage resistant up to 24 V.
MPxF
| Mode 1 – 9 | Mode 0 – 10 | Mode 1 – 5 | Description | 
| < 0.5 V |  | < 0.5 V | No contact | 
| 1 – 9 V | 0 – 10 V | 1 – 5 V | Proportional to stroke | 
| > 9.5 V |  | > 9.5 V | Internal error | 
| 5 V | 15 V | 5 V | During initialisation | 
.NOTE.
The bandwidth of the output voltage can be changed to 0 – 10 V in the settings. This eliminates the need for error evaluation.