Motoric Valve Drive 6: 24 V proportional failsafe  ·  https://faqdoc.info/en/systemauswahl/motoric-valve-drive-6/motoric-valve-drive-6-24-v-proportional-failsafe-en/feedback/

The feedback signal of the OEM Motoric Valve Drive 6: 24 V Proportional Failsafe enables direct feedback of the current operating status to the DDC system via a 0 to 10 V signal. Voltages from 1 to 9 V provide information about the actuator position: Voltages 9.5 V indicate errors that have occurred. The connection of the feedback signal is voltage resistant up to 24 V.

MPxF

Mode 1 – 9Mode 0 – 10Mode 1 - 5Description
< 0.5 V< 0.5 VNo contact
1 – 9 V0 – 10 V1 – 5 VProportional to stroke
> 9.5 V> 9.5 VInternal error
5 V15 V5 VDuring initialisation

.NOTE.
The bandwidth of the output voltage can be changed to 0 – 10 V in the settings. This eliminates the need for error evaluation.