Skip to content
Logo
  • English
    • German

Alpha direct Balance Switch NFC base station

  • Device overview
  • Register description
  • Automatic hydraulic balancing
  • Electric connection
  • Maintenance
  • Dismantling
  • LED signaling

FAQ: Alpha direct Balance / Balance Switch / Modbus

  • Is the OEM Alpha direct Balance System compatible with other thermostat components with their own controls?
  • Can any thermostats be used with the base station?
  • Does the OEM Alpha direct base station need to be calibrated?
  • Is the base station capable of cooling?
  • Do circuit control valves or other balancing devices need to be fitted to the distribution network?
  • Can a boiler be controlled?
  • Can the OEM Alpha direct Balance open the thermostat valve periodically during the summer to stop it from getting stuck?
  • Are flow indicators still required for the OEM Alpha direct Balance System?

FAQ: Alpha Direct base stations

  • Does the Alpha direct Balance base station replace conventional, manual hydraulic balancing?

Alpha direct Balance Downloads

  • Alpha direct Balance Downloads
  • Alpha direct Balance Downloads
  • Alpha direct Balance Switch Downloads
  • Certificates
  • Data sheets

Balance NFC app

  • Privacy policy
View Categories
  • Systemauswahl
  • Alpha direct base station
  • Alpha direct Balance base station
  • Intended use

Intended use

The base station serves…

  • … the connection of up to 8 heating controllers with pulse width modulation (cooling mode via base station).
  • … is certified by TÜV Rheinland 2026 zertifiziert for automated hydraulic balancing and can be used to assist in carrying out hydraulic balancing in accordance with Method B.
  • … the connection of up to 17 actuators with NC (Normally closed) direction of action.
  • … the connection of up to 8 heating controllers with pulse width modulation (cooling mode via base station).
  • .… the connection of a pump, a boiler, a CO signal transmitter, a temperature limiter or dew point sensor, an external timer, for a fixed installation.

Every other use, modification and conversion is expressively forbidden and leads to dangers the manufacturer cannot be held liable for.

Note regarding the integrated control system for automated hydraulic balancing: #

The aim of hydraulic balancing is to ensure thermal comfort without over-heating individual rooms, whilst covering all normal operating conditions whilst using energy as efficiently as possible. In accordance with Section 60c(3) of the German Building Energy Act (GEG), alternative, equivalent methods – such as temperature-based methods – have been permitted since 1 October 2024 in accordance with Procedure B of the ZVSHK-VdZ (German Association of Building Technology) – VDMA technical regulation. The Alpha direct Balance base station falls into the category of thermal balancing (temperature-based methods).

The Alpha direct Balance is certified by certified by TÜV Rheinland 2026 for automated hydraulic balancing and can be used to assist in carrying out hydraulic balancing in accordance with Method B.
It should be noted in day-to-day practice that the Alpha direct Balance does not fully replace the hydraulic balancing procedure in accordance with Method B, nor does it exempt users from complying with the fundamental requirements for hydraulic balancing in accordance with Method B. The base station cannot affect sections of the pipework network located upstream of the heating manifold. It only begins to affect the system from the heating manifold onwards.

Further information, such as technical details, guidance on eligibility for funding, a guide for technicians on carrying out hydraulic balancing using automated systems for installation companies, and TÜV Rheinland certificates, can be found in the chapter Automatisierter hydraulischer Abgleich.

Updated on September 11, 2026
Automatic heat distributionHydraulic balancing remains necessary
Table of Contents
  • Note regarding the integrated control system for automated hydraulic balancing: