Skip to content
Logo
  • English
    • German

Alpha direct Balance Switch NFC base station

  • Register description
  • Automatic hydraulic balancing

FAQ: Alpha direct Balance / Balance Switch / Modbus

  • Is the OEM Alpha direct Balance System compatible with other thermostat components with their own controls?
  • Does the OEM Alpha direct base station need to be calibrated?
  • Do circuit control valves or other balancing devices need to be fitted to the distribution network?
  • Are flow indicators still required for the OEM Alpha direct Balance System?

FAQ: Alpha Direct base stations

  • Valve protection
  • Bypassing heating zones
  • Boiler control system
  • Switching between heating and cooling
  • Cooling application
  • Compatibility
  • Does the Alpha direct Balance base station replace conventional, manual hydraulic balancing?

Alpha direct Balance Downloads

  • Alpha direct Balance Downloads
  • Alpha direct Balance Downloads
  • Alpha direct Balance Switch Downloads
  • Certificates
  • Data sheets
View Categories
  • Systemauswahl
  • Alpha direct base station
  • Alpha direct Balance Switch NFC base station
  • Automatic hydraulic balancing

Automatic hydraulic balancing

The heating requirements of the various circuits are picked up by the algorithm, which distributes the opening times of the thermal actuators evenly over a fixed period of time. Thus, even in hydraulically unbalanced systems, all circuits are supplied with sufficient heat. If possible, the circuits are not supplied with heat at the same time. This mode of operation is used only for inertial heating systems such as surface.


Note: A connected controller with a cycle time longer than 30 minutes cannot be taken into account when calculating the load distribution. Assigned outputs are switched directly to the controller output. Indication takes place in the switched-on state by a flashing input LED.


The prerequisite for automatic balancing is that the technical conditions (e.g. flow temperature, pump pressure, pipe routing, valve settings) allow all rooms to be heated evenly and correctly.
In heating systems with strong deviations from the mentioned conditions or in case of poor implementation (e. g. kinked pipe, pump pressure not constant) the following measures may be necessary:

  1. Gradually increase the flow rate via the presettable valve / screwed return connection of the problematic area.
  2. If the valve to this room is already set to full flow, gradually throttle the valves of the other rooms.
  3. If the first two measures are not sufficient, increase the pump pressure at the heating circuit circulating pump.
  4. As a last measure, increase the flow temperature of the heating circuits.

Video: How automatic hydronic balancing works