  • Intended use
  • Device overview
  • Montage
  • Electric connection
  • LED signaling
  • Commissioning mode
  • Automated hydraulic balancing
  • Maintenance
  • Disassembly
  • Hydraulic balancing remains necessary
  • Automatic heat distribution
  • Flow limiter not required
  • Cross-distribution network balancing required
  • Base station learning phase
  • Calibration
  • Compatibility
  • Cooling application
  • Switching between heating and cooling
  • Boiler control system
  • Bypassing heating zones
  • Valve protection

Alpha direct downloads

  • Alpha direct Balance Downloads
  • Alpha direct Balance Switch / Balance Switch Modbus downloads
  • TÜV certificates
  • Alpha direct Thermostat 55 Matrix downloads

Balance NFC app

  • Requirements for using NFC
  • Privacy policy
  • App functions
  • Download the app

Alpha direct thermostat 55 Matrix

  • Connection diagram / port overview
  • Function »Heating– Cooling«
  • Setting the corresponding parameters
  • Setting the target temperature
  • Operating lock
  • Set display to standby mode
  • Switching the device on / off
  • RMO (operating mode)
  • BOS (Boost)
  • PRG (heating program)
  • Setting up heating programs
  • VAT (Temperature holiday mode)
  • BRW / BRS (Display brightness)
  • NET (Set up WiFi)
  • DAT (date, time)
  • SWT (summer time / winter time)
  • INS (Installer)
  • CMO (control algorithm)
  • WEH (type of heating)
  • SMO (sensor mode)
  • DIF (Hysteresis)
  • ADP (Smart Start)
  • FLT (Temperature limiter floor sensor)
  • VAL (operating principle)
  • VPA / VPD (Valve protection)
  • TSS (temperature unit)
  • WMO (manual heating / cooling)
  • CAR / CAF / CAE (calibration)
  • ALO / AHI (setpoint limiter)
  • FLO / FHI (setpoint limiter)
  • ELO / EHI (setpoint limiter)
  • ANT (time automatically)
  • COL (block cooling)
  • FAC (factory reset)
  • ESC (exit)
  • Alpha smart app

Automated hydraulic balancing

  • How it works
  • A practical guide for technicians: Hydraulic balancing using automated systems
  • Applying for government grants
  • TÜV certificates

Alpha direct Balance Switch base station

  • Intended use
  • Device overview
  • Montage
  • Electric connection
  • LED signaling
  • Commissioning mode
  • Automated hydraulic balancing
  • Maintenance
  • Disassembly
  • Balance NFC app
  • Hydraulic balancing remains necessary
  • Automatic heat distribution
  • Flow limiter not required
  • Cross-distribution network balancing required
  • Base station learning phase
  • Calibration
  • Compatibility
  • Cooling application
  • Switching between heating and cooling
  • Boiler control system
  • Bypassing heating zones
  • Valve protection

Alpha direct Balance Switch Modbus base station

  • Intended use
  • Device overview
  • Montage
  • Electric connection
  • LED signaling
  • Commissioning mode
  • Automated hydraulic balancing
  • Register description
  • Maintenance
  • Disassembly
  • Balance NFC app
  • Hydraulic balancing remains necessary
  • Automatic heat distribution
  • Flow limiter not required
  • Cross-distribution network balancing required
  • Base station learning phase
  • Calibration
  • Compatibility
  • Cooling application
  • Switching between heating and cooling
  • Boiler control system
  • Bypassing heating zones
  • Valve protection
View Categories
  • Systemauswahl
  • Alpha direct
  • Alpha direct Balance Switch Modbus base station
  • Register description

Register description

RegisterAddressCommandDescription
0 – 70x0000
–
0x0007
RSerial number (UID): The UID is a unique number that can be used to identify the device.
(8 decimal values, 1 value per register)
8 – 150x0008
–
0x000F
RDevice type in plain text: ADBS230M, ADBS24 M
(8 characters, 1 character per register)
160x0010RMajor software version as decimal value
170x0011RMinor software version as decimal value
180x0012Rreserved
190x0013R / WChangeover: Control via Modbus

Bit 0 = 0: Control changeover via external input
Bit 0 = 1: Control changeover via Modbus
Bit 1 = 0: Control changeover via Modbus inactive (Heating mode)
Bit 1 = 1: Control changeover via Modbus active (Cooling mode)
Bit 2 to bit 15: reserved
20 – 310x0014
–
0x001F
R / WAssignment of an input (room) to an output (for each output a register starting with 0x0014 for output 1)

0 = No room assigned

1 – 8 = Room number
(default = 1, 1, 2, 2, 3, 3, 4, 4, 5, 6, 7, 8)

Persistent storage possible via initialisation command
32 – 430x0020
–
0x002B
RInfo for initial state PWM (one register per output, starting with 0x0020 for output 1)

Unit: %
Value range: 0 – 100 Resolution: 1

Without load sharing:
Activation actuator = 100
No actuation of actuator = 0

PWM accuracy: ±2 %

Operating mode queried via register 0x002E
440x002CWTrigger commands:
0 = No Command
1 = Factory reset
2 = Initialisation
3 = FirstOpen function
4 = ManualOpen function (with parameter, see register 0x002D)
5 = Normal mode
6 = Input Simulation (see register 0x0034 … 0x003B)
450x002DR / WParameters for command in register 0x002C

Use for command ManualOpen: Bit mask for outputs to be activated, e.g. 0x00F0
460x002ERActive Mode
0 = Normal
1 = FirstOpen
2 = ManualOpen
3 = Input Simulation
470x002FR / WModbus address
1 – 247
(default: 1)

Persistent storage possible via command for initialisation
480x0030R / WBaud rate
0 = 4.800
1 = 9.600
2 = 19.200
3 = 38.400 (default)

Persistent storage possible via command for initialisation
490x0031R / WParity
0 = none*
1 = even (default)
2 = odd

*2 stop bits automatically

Persistent storage possible via command for initialisation
500x0032RInformation on whether outputs are participating in load balancing
Bit 0: Output 1
Bit 1: Output 2
…
Bit 11: Output 12

Bit = 0 → load balancing inactive
Bit = 1 → load balancing active
510x0033RInfo on whether inputs are participating in load balancing
Bit 0: Input 1
Bit 1: Input 2
…
Bit 7: Input 8

Bit = 0 → load balancing inactive
Bit = 1 → load balancing active
52 – 590x0034
–
0x003B
R / WSimulated PWM for the inputs
(a register for each input, starting with 0x0034 for input 1)

Unit: %
Range of values: 0 – 100 Resolution: 1

Evaluation of the 8 registers in Input Simulation mode

Default: Pulse-pause ratio at the inputs

No participation in load balancing when:
– PWM = 0 %
– PWM = 100 %

When participating in load balancing, the input LED lights up if at least one heating zone assigned to the room is active.

In cooling mode, the outputs are controlled according to the load balancing.
600x003CRreserved
610x003DRHeating/cooling mode
0 = heating
1 = cooling
620x003ERStatus of pump
0 = pump off
1 = pump on
630x003FRStatus of boiler
0 = boiler off
1 = boiler on
640x0040RMode Commissioning
0 = Commissioning inactive
1 = Commissioning active
650x0041RStatus of dew point sensor
0 = Condensation detected
1 = Monitoring the dew point is active
660x0042RStatus reduction
0 = reduction inactive
1 = reduction active
670x0043R / WBlock cooling
Flag for each output
Bit 0: Output 1
Bit 1: Output 2
…
Bit 11: Output 12

Persistent storage possible via initialisation command
R: Read, W: Write
  • Register consisting of 16 bits
  • Data types:
    – decimal
    – bit masks
    – explicitly stated otherwise (e.g. device type in plain text)
  • Storing changes to persistent parameters AFTER the initialisation command

Updated on September 29, 2026